Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
- Bi-directional measurement IMP & EXP
- Two pulse outputs
- RS485 Modbus
- Din rail mounting 35mm
- 100A direct connection
- Better than Class 1 / B accuracy
Application
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like residential, Utility and Industrial application. The unit measures and displays various important electrical parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy measurement makes the unit a good choice for solar PV energy metering.
General Specifications | |
---|---|
Voltage AC (Un): | 230V |
Voltage Range | 176~276V AC |
Base Current (Ib) | 10A |
Max. Current (Imax) | 100A |
Mini Current (Imin) | 0.5A |
Starting current | 0.4% of Ib |
Power consumption | <2W/10VA |
Frequency | 50/60Hz(±10%) |
AC voltage withstand | 4KV for 1 minute |
Impulse voltage withstand | 6KV-1.2uS wavform |
Overcurrent withstand | 30Imax for 0.01s |
Pulse output rate | 1000imp/kWh (default) 1000/100/10/1 imp/kWh/kVarh (configurable) |
Display | LCD with blue backlit |
Max. Reading | 999999.9kWh |
Accuracy
Voltage: 0.5% of range maximum
Current: 0.5% of nominal
Frequency: 0.2% of mid-frequency
Power factor: 1% of Unity
Active power: 1% of range maximum
Reactive power: 1% of range maximum
Apparent power: 1% of range maximum
Active energy Class: 1 IEC62053-21
Class: B EN50470-3
Reactive energy: 1% of range maximum
Environment
Operating temperature: -25℃ to +55℃
Storage and transportation temperature: -40℃ to +70℃
Reference temperature: 23℃±2℃
Relative humidity: 0 to 95%, non-condensing
Altitude up to: 2500m
Warm up time: 10s
Installation category: CAT III
Mechanical Environment: M1
Electromagnetic environment: E2
Degree of pollution: 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with import kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Mechanics
Din rail dimensions: 36x99x63 (WxHxD) DIN 43880
Mounting DIN rail: 35mm
Sealing: IP51 (indoor)
Material: self-extinguishing UL94V-0